Product Overview
AS14F Industrial Relay is a relay documented with a 1Z contact form, a rated load of 12A 250VAC/30VDC, AgSnO₂ AgNi contact material.
Key Features
● Fast response
● Slim size
● High rated Load 1Z 12A; 2Z 8A
Technical Specifications
| Specifications | |||
| Contact | Contact Form | 1Z | 2Z |
| Rated Load | 12A 250VAC/30VDC | 8A 250VAC/30VDC | |
| Electrical/Mechanical Life | ≥100000times/10000000times | ||
| Initial Contact Resistance | ≤100mΩ (1A 6VDC) | ||
| Contact Material | AgSnO₂ AgNi | ||
| Characteristics | Insulation Resistance | ≥500MΩ (500VDC) | |
| Dielectric Strength | Between open contacts≥1000VAC/1min | ||
| Between poles≥1500VAC/1min | |||
| Between contact and coil≥4000VAC/1min | |||
| Operate/Release Time | ≤15ms/15ms | ||
| Terminal Type | Plug in | ||
| Coil | Operating Power DC/AC | 0.53W/0.9VA | |
DC Coil Data
| Rated Voltage (VDC) | Pickup Voltage (VDC) | Dropout Voltage (VDC) | Coil Resistance (Ω±10%) |
| 3 | 2.25 | 0.3 | 17 |
| 5 | 3.75 | 0.5 | 47 |
| 6 | 4.5 | 0.6 | 68 |
| 9 | 6.75 | 0.9 | 150 |
| 12 | 9 | 1.2 | 270 |
| 18 | 13.5 | 1.8 | 610 |
| 24 | 18 | 2.4 | 1100 |
| 48 | 36 | 4.8 | 4220 |
| 110 | 82.5 | 11 | 22800 |
AC Coil Data
| Rated Voltage (VAC) | Pickup Voltage (VAC) | Dropout Voltage (VAC) | Coil Resistance (Ω±10%) |
| 6 | 4.8 | 1.8 | 16 |
| 12 | 9.6 | 3.6 | 65 |
| 24 | 19.2 | 4.2 | 240 |
| 48 | 38.4 | 14.4 | 1080 |
| 115 | 88 | 33 | 6300 |
| 230 | 184 | 69 | 23000 |
Technical Data and Drawings
Ordering Information

Dimensions (mm)

Wiring Diagram

Frequently Asked Questions
What is the rated load?
The documented rated load is 12A 250VAC/30VDC.
What contact material is specified?
The specified contact material is AgSnO₂ AgNi.
What insulation resistance is specified?
The specified insulation resistance is ≥500MΩ (500VDC).















Reviews